2 Fir eShield Plus O n e t o T e n C o n v e n t i o n a l I n p u t Z o n e s F i r e A l a r m C o n t r o l P a n e l s Standar d Featur es • Fr ont panel pr ogramming • Compatible with CleanMe® devices, which advises when dirty • 1, 3, 5 and 10 initiating device cir cuits (IDC) • 1, 2 or 4 signal cir cuits (NAC) • Optional Class A IDC & NAC cir cuits • Supports EC, C2M, EDW and 6200 Series detectors • One person device testing (audible or silent) • Combination waterfow and supervisory IDC • Optional fr e department module or integrated dact/dialer • Optional serial bus annunciators and r elays Application Fir eShield Plus pr ovides smoke and fr e detection, occupant notifcation and of f-pr emises signaling for small to medium sized buildings. The Fir eShield single-zone panel has one initiating device cir cuit (IDC) and one notifcation appliance cir cuit (NAC). The IDC can be confgur ed for alarm, with or without alarm verifcation. Each IDC on the 3, 5 and 10 zone can be confgur ed for one of eight operating modes. The modes ar e: • Alarm - without smoke detector verifcation • Alarm - with smoke detector verifcation and instant activation of contact devices • W aterfow alarm - no r etar d • W aterfow alarm - with 15 second r etar d • Combination waterfow (no r etar d) and supervisory • Combination waterfow (r etar d) and supervisory • Supervisory (latching) • Monitor - for monitoring devices other than alarm or supervisory such as fr e doors or fr e dampers NACs can be individually confgur ed for one of thr ee outputs. These ar e Genesis, Continuous or T emporal. The Genesis selection eliminates the need to install a Genesis Signal Master . When confgur ed for Genesis notifcation appliances the Alarm Silence function will silence any Genesis audible appliance but Genesis str obes will r emain active until the panel is r eset. Both the hor ns and str obes on Genesis notifcation appliances will be synchr onized acr oss all NACs when the Genesis mode is selected. Overview The Fir eShield Plus fr e alarm family consists of 1, 3, 5 and 10 zone conventional fr e alarm contr ol panels, an integrated DACT/Dialer , serial annunciator modules and serial r emote r elay modules. All of these components ar e micr opr ocessor contr olled. The Fir eShield family is ideal for both new and r etr oft installations. Fir eShield incorporates featur es designed to simplify installation, operation and maintenance. These include fr ont panel pr ogram - ming, one person walk testing, selectable IDC and NAC types. Fir eShield is powerful enough to meet the demands of today’ s installations. The FSP101 single zone power supply pr ovides 1.0 amp of curr ent for notifcation appliances (0.1 amps can be used for auxilary curr ent). The 3, 5 and 10 zone panel power supplies pr ovide 4.25 amps of curr ent. 3.5 amps can be used for notifcation appliances and 0.5 amps can be used as auxiliary curr ent. The 10 zone panel will support an additional 3.25A when an optional second transformer (P/N F-XTR120) is installed in the panel. The 5 and 10 zone contr ol panels can be confgur ed for Class B and Class A operation. The 1 and 3 zone contr ol panels ar e confgur ed for Class B operation only . Remote Annunciator and Relays The serial bus standar d on Fir eShield models FSP302, FSP502 and FSP1004 is another installation time saver . This cir cuit allows the connection of Remote System Indicators. Remote Zone Indicators and Remote Relay Modules over a four -wir e cir cuit (data and power). Annunciator and r elay modules can be installed up to 1000 feet fr om the panel on 18-gauge wir e. CONTINUES... F S P 5 0 2 G